BV Building Wires

Single-core copper building wires with PVC insulation for fixed electrical wiring. They are suitable for power supply in residential, commercial and industrial buildings.

BV Building Wires | PVC Insulated Copper Wire

Product Overview

BV building wires are designed for fixed electrical installations. Each wire has a solid or stranded rigid copper conductor. This cable is covered with PVC insulation, without an outer sheath.

BV building wires have a simple construction. They are suitable for fixed wiring installed in conduits, trunking and other protected routes. They are commonly used for lighting circuits, socket circuits and connections within building distribution systems.

Vastcore Cable can supply BV wires in different conductor sizes and insulation colours according to your wiring schedule and project requirements. Confirm the required voltage rating, conductor construction and applicable standard when requesting a quotation.

Applications

BV building wires are used for fixed wiring where the installation provides suitable mechanical protection.

utility power distribution network with medium voltage cable installation

Residential Wiring

For lighting and socket circuits in houses and apartment buildings.

low-voltage-power-distribution-using-PVC-power-cables_720x440

Commercial Buildings

For fixed electrical wiring in offices, shops and public buildings.

commercial and residential wiring projects with PVC cables

Conduits and Trunking

For individual circuit wires routed through suitable conduits or enclosed trunking.

underground and outdoor power distribution cable installation

Distribution Equipment

For fixed connections in distribution boards and electrical cabinets, where the specified installation method permits their use.

CHARACTERISTICS

Voltage Rating Uo/U

Typically 450/750 V for the specified BV building wire range; confirm the rating for each ordered size.

Conductor Type

Single-core rigid copper conductor, solid or stranded according to the wire size and specification.

Insulation

PVC insulation in colours selected to match the project wiring requirements.

Operating Temperature

Maximum continuous conductor temperature of 70°C for standard PVC insulated construction.

industrial electrical installation using PVC insulated cables

Cable Construction

The cable consists of a stranded aluminum conductor, XLPE insulation and a PVC outer sheath. Construction details can be adjusted according to project specifications and applicable standards.

Item Description
Conductor
Solid or stranded rigid copper conductor
Conductor Class
Class 1 or Class 2, as specified
Insulation
PVC compound
Outer Sheath
None

Reference Standards:GB/T 5023.3 and IEC 60227-3 may be used as references, subject to the specification and compliance requirements agreed for the order.

Cable Sizes & Technical Parameters

Nominal Size
(mm²)
Conductor Type Max. DC Resistance
(Ω/km, 20°C)
Insulation Nominal
Thickness (mm)
Approx. Outer
Diameter (mm)
Approx. Weight
(kg/km)
1×1.5
Stranded, Class 2
12.1
0.7
2.9
22
1×2.5
Stranded, Class 2
7.41
0.8
3.6
32
1×4
Stranded, Class 2
4.61
0.8
4.1
50
1×6
Stranded, Class 2
3.08
0.8
4.7
71
1×10
Stranded, Class 2
1.83
1
5.9
110
1×16
Stranded, Class 2
1.15
1
6.8
164
1×25
Stranded, Class 2
0.727
1.2
8.4
256
1×35
Stranded, Class 2
0.524
1.2
9.4
346
1×50
Stranded, Class 2
0.387
1.4
11
473
1×70
Stranded, Class 2
0.268
1.4
12.7
674
1×95
Stranded, Class 2
0.193
1.6
14.7
913
1×120
Stranded, Class 2
0.153
1.6
16.2
1150
1×150
Stranded, Class 2
0.124
1.8
18
1416
1×185
Stranded, Class 2
0.0991
2
20
1749
1×240
Stranded, Class 2
0.0754
2.2
23
2317
1×300
Stranded, Class 2
0.0601
2.4
25.2
3049
1×400
Stranded, Class 2
0.047
2.6
28.4
3657

Why Choose Vastcore Cable

Sizes and Colours for Your Wiring Schedule

Specify the conductor sizes, insulation colours and quantities needed for each circuit or project area.

Clear Specification Review

We check the voltage rating, conductor construction and required standard before preparing a quotation.

Order and Shipping Coordination

Packing, inspection documents and shipping details can be arranged according to the confirmed order requirements.

START YOUR PROJECT

Ready to Discuss Your BV Wire Requirements?

Send us your conductor sizes, insulation colours, required quantities and destination. We will review your specification and prepare a quotation.